Chlorine Dioxide Generator SafeOx 614
 
Home
Chlorine Dioxide
Chlorine Dioxide Generators
Applications Test Kits About Us FAQ Contact Us  
 
   

Chlorine Dioxide Generator - SafeOx 614

The SafeOx 614 chlorine dioxide generator comprises a simple panel-mounted, two-part generating system that uses sodium chlorite and hydrochloric acid in the presence of a unique catalyst to generate significantly greater levels of ClO2 than traditional production methods. Each SafeOx generating system is built to the highest manufacturing standards, and is designed for continuous operation in sterilisation units, cooling towers and other industrial and commercial applications.

Chlorine Dioxide Per Day

The SafeOx 614 system will generate up to 0.614 Kg (1.35 pounds) of chlorine dioxide per day.

Catalyst Column

This generator system operates in conjunction with the SafeOx RC 614 catalyst column.

Precursor Specifications

    • SafeOx approved sodium chlorite solution.
    • SafeOx approved hydrochloric acid.
    • SafeOx catalytic reactor.

Important Notice: The use of precursors other than those specified by SafeOx and operating outside the recommended parameters invalidates any warranty given with this equipment.

Feed Water

The feed water must be potable or equivalent. It cannot be chemically treated process or cooling water. Additives or contaminants not approved at potable levels will affect the performance of the system and purity of the chlorine dioxide product. Performance, efficiency and lifespan are partly determined by the physical and chemical characteristics of the water. SafeOx assumes that the following specifications have been met.

Temperature - The allowable feed water temperature range is 41 to 95 °F (5 to 35 ºC). If the feed water temperature is not within specification, a simple heat exchanger (coiled copper tubing, heat tape, etc.) may be useful.

Pressure - A minimum feed water pressure of 30 psi (2.04 bar) is required. A pressure-reducing valve on the system may be used to lower incoming pressure. Avoid feeding the system from make-up lines with frequent pressure drops and fluctuations.

Product Delivery - These SafeOx systems will dose into pressurised lines up to 20 psi maximum. For dosing into lines above 20 psi, a SafeOx Dosing Package is required.

Environmental Conditions - Avoid locations where the systems will be subjected to extreme cold or heat, i.e., below 5 °C (41 °F) or above 45 °C (614 °F), direct sunlight, vibration, vapours, liquid spills or EMI (electromagnetic interference i.e. strong radio transmission and electric motors). The systems could be damaged which will invalidate the warranty.

Electrical - The systems must be wired in accordance with all applicable electrical codes. These SafeOx units are fuse protected (replaceable plug-in 5 amp fuse on the relay board) and single voltage 115 VAC, 5 Amperes, 60 Hz. The systems can operate at 50 Hz with a ~16 % loss in pump efficiency. The output relays are also individually fuse protected. Use of a surge protector is recommended.

Physical Specifications of SafeOx Generators

    • Dimensions - 91 cm X 61 cm X 20 cm (36 inch X 24 inch X 8 inch).
    • Weight (operational) - 27 kg (60 pounds).
    • Pumps (2) - MasterFlex® peristaltic with Norpreneä tubing.
    • Reactor - A specially designed reactor allows for optimum reaction efficiency of the chlorite-acid solution rite-acid solution.
    • Electrical Source - 115 or 230 volt, 60 Hz (50 Hz with a ~16 % loss in pump efficiency).
    • Solenoid Valve - Direct action, 2-way solenoid valve protects the system during non-service operation.
    • Flow Switch - This switch shuts down the two pumps if a flow loss is detected.
    • Flow Controller - This device maintains a constant flow rate from 25 to 100 psi (1.72 to 6.9 bar).
    • Remote On/Off - Two terminal blocks are provided. Connecting a 120 VAC rated contact will provide remote operation. Close contact to operate.
    • ClO2 Flow Rate - Approximately 160 ml/min.
    • ClO2 Concentration - Approximately 380 ppm.
    • Efficiency - 85% or more.

Important Notice: It is the responsibility of the SafeOx operator to properly apply the chlorine dioxide and to understand the relevant local and international regulations concerning the use of chlorine dioxide.

Additional Information

For more information about SafeOx products please call us on +44 (0) 161 877 2334 or e-mail info@safeox.com.

 

Back to top

 

 


 
   

 

Home

Generators

About Us

Chlorine Dioxide

Applications

FAQ

 

 

ClO2 Testing

Contact Us

Media

Privacy

Disclaimer

Site Map

 

©2008 SafeOx - Chlorine Dioxide